dc.description.abstractThe aim of the Best Vent project was to find the optimal control strategy for demand-controlled ventilation (DCV) without compromising on indoor air quality. In this paper, we discuss control strategies that would ensure acceptable perceived air quality for unadapted users. This study is a part of a series of field studies where sensory panels of untrained persons visited classrooms at a school. The sensory panel visited classrooms occupied by different user groups, at different ventilation rates and temperatures, and in empty classrooms at different ventilation rates, and with different pollutant loads. This study aims to assess whether it would be reasonable to control the supply airflow rate towards a higher CO2 setpoint at low air temperature, and still maintain the same perceived indoor air quality upon entry. The results indicate that the perception of indoor air quality does not deteriorate at higher CO2 concentrations when the air temperature is kept at 21 ◦C as opposed to at 24 ◦C. Furthermore, an increase in air temperature yielded poorer perceived air quality scores at similar CO2 concentrations in the classrooms. Our results indicate that a DCV-control strategy with a higher CO2 setpoint in classrooms at low temperatures would not compromise perceived air quality. Further research would be needed to assess whether the same is true for indoor climate-related symptoms or performance.en_US
dc.description.sponsorshipBEST VENT is funded by the Research Council of Norway EnergiX program under Grant 255375/E20 together with the following Norwegian industry partners: Undervisningsbygg Oslo KF, GK Inneklima AS, DNB Næringseiendom AS, Erichsen & Horgen AS, Multiconsult AS, Interfil AS, Camfil Norge AS, Swegon AS, Belimo Automasjon Norge AS, Toma Eiendomsdrift AS, Norsk VVS Energi- og Miljøteknisk Forenings Stiftelse for forskning.en_US
dc.language.isoengen_US
dc.publisherElsevieren_US
dc.relation.ispartofseriesBuilding and Environment;Volume 205, November 2021, 108180
dc.rightsNavngivelse 4.0 Internasjonal*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/deed.no*
dc.subjectPerceived air qualityen_US
dc.subjectOdour intensityen_US
dc.subjectDemand-controlled ventilationen_US
dc.subjectSchoolsen_US
dc.subjectIndoor air qualityen_US
dc.titleTemperature-dependent ventilation rates might improve perceived air quality in a demand-controlled ventilation strategyen_US
dc.typePeer revieweden_US
dc.typeJournal articleen_US
dc.description.versionpublishedVersionen_US
dc.rights.holder© 2021 The Authors.en_US
dc.source.articlenumber108180en_US
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode2
dc.identifier.doihttps://doi.org/10.1016/j.buildenv.2021.108180
dc.identifier.cristin1924902
dc.source.journalBuilding and Environmenten_US
dc.source.volume205en_US
dc.source.pagenumber1-8en_US
dc.relation.projectNorges forskningsråd: 255375en_US


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel

Navngivelse 4.0 Internasjonal
Med mindre annet er angitt, så er denne innførselen lisensiert som Navngivelse 4.0 Internasjonal