CFD analysis of displacement ventilation
Bachelor thesis
Permanent lenke
https://hdl.handle.net/20.500.12199/1273Utgivelsesdato
2018-05-23Metadata
Vis full innførselSamlinger
Sammendrag
Displacement ventilation is an air supply method that uses supplied air near the floor at low velocity and fewer degrees below the air in the room. Well-designed displacement ventilation gives sufficient air quality, thermal comfort in the occupied zone as well as energy saving since free cooling can be used.
The problem that was introduced to us was that laboratory measurements and CFD simulations have had inconclusive results in regards to the correctness of the Archimedes number proposed in the Nordtest method NT VVS 083. STAR-CCM+ has been used in this study to conduct simulations concerning this problem. With varying diffuser heights, inlet flow rates and heat loads, there were no significant changes in the Archimedes number. However, this was done with 20% increment of diffuser height. Further research is required to determine if the Archimedes number should include a length scale for diffuser height.
Beskrivelse
Bachelor i Ingeniørfag- energi og miljø i bygg